Key Product Information


​Red Edge Pulse Protection

Our Red Edge advantage includes the knowledge and expertise gained from almost 90 years of designing and building RF shield and filter solutions for demanding defense and commercial applications.​ 

EMP Pulse Protection

The filter unit is fitted with inductive input circuit and ESA, resulting in very low residual currents during an EMP pulse, protecting connected equipment.​  

Insertion Loss Performance as Required by MIL-STD-188-125 1 & 2

Our filters provide 80 dB of insertion loss across a frequency range of 10 MHz to 1 GHz and 100 dB from 1 GHz to 20 GHz in symmetric and asymmetric mode per MIL-STD-220.​ 

High Frequency Response Design

Better frequency response is achieved with the use of a high frequency feed-through capacitor design.​ Extended filter life oversized inductors are used for low loss and low temperature rise which extends filter life. Filter life is further extended with the use of self-healing capacitors.​​​

Meets or Exceeds These Standards

  • MIL-STD-188-125 1 & 2 

  • Defense Standard 59-188 1 & 2 

  • MIL-STD-F15733

  • MIL-STD-220 

  • UL 1283 5th ed.

  • CSA C22, 2 No. 8 (R2008)

  • IEC 60939

  • LVD (2066/95/EC) 

Listed Tests Performed

  • MIL-STD-188-125 by Little Mountain Test Facility, Hill AFB, Ogden, UT

  • UL1283, by Intertek ETL 

Test Performance Results 

  • Frequency Insertion Loss in Symmetric and Asymmetric Mode

    • 80 dB, 10 MHz to 1 GHz 

    • 100 dB, from 1 GHz to 20 GHz

  • Pulse Suppression Performance MIL-STD-188-125 Acceptance Test: Short Pulse Current Injection (E1), Wave Shape 20/500 ns 

  • Pulse Suppression Performance MIL-STD-188-125 Acceptance Test: Intermediate Pulse Current Injection (E2), Wave Shape 1.5/3000 μs

  • Listed for Safety to UL 1283 and CSA C22, 2 No. 8 by Intertek ETL​ 

Specifications Select a tab below for more information



Model

Amperage

Short Circuit Current Rating (SCCR)

Max Voltage

Input Pulse Amplitude, E1, E2

Residual Requirement Amplitude and Filter Residual Let Through

Typical Filter Response

HEMP-2010

10

10 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-2030

30

25 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-3030

30

25 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-4030

30

25 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-2060

60

25 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-3060

60

25 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-4060

60

25 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-2100

100

25 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-3100

100

25 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-4100

100

25 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-3250

250

25 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-4250

250

25 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-3X400

400

50 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-4X400

400

50 k A

277/480

2500 A; 250 A 

<10 A 

1No Filter Damage or Performance Degradation 

HEMP-3X600

600

125 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-4X600

600

125 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-3X800

800

125 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation n

HEMP-4X800

800

125 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-3X1200

1200

150 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 

HEMP-4X1200

1200

150 k A

277/480

2500 A; 250 A 

<10 A 

No Filter Damage or Performance Degradation 


Model

Wires

Wall Mount Cabinet

Floor Mount

Nominal Dimensions H x W x D

HEMP-2010

2

Yes

No

43 cm x 10 cm x 8 cm (17 in x 4 in x 3 in)

HEMP-2030

2

Yes

No

51 cm x 13 cm x 9 cm (21 in x 5 in x 3.5 in)

HEMP-3030

3

Yes

No

53 cm x 25 cm x 9 cm (21 in x 10 in x 3.5 in)

HEMP-4030

4

Yes

No

53 cm x 25 cm x 9 cm (21 in x 10 in x 3.5 in)

HEMP-2060

2

Yes

No

107 cm x 25 cm x 25 cm  (2 in x 10 in x 10 in)

HEMP-3060

3

Yes

No

107 cm x 51 cm x 25 cm (42 in x 20 in x 10 in)

HEMP-4060

4

Yes

No

107 cm x 51 cm x 25 cm (42 in x 20 in x 10 in)

HEMP-2100

2

Yes

No

107 cm x 25 cm x 25 cm (42 in x 10 in x 10 in)

HEMP-3100

3

Yes

No

107 cm x 51 cm x 25 cm (42 in x 20 in x 10 in)

HEMP-4100

4

Yes

No

107 cm x 51 cm x 25 cm (42 in x 20 in x 10 in)

HEMP-3250

3

Yes

No

152 cm x 61 cm x 25 cm (60 in x 24 in x 10 in)

HEMP-4250

4

Yes

No

152 cm x 61 cm x 25 cm (60 in x 24 in x 10 in)

HEMP-3X400

3

Yes

Yes

173 cm x 86 cm x 30 cm (68 in x 34 in x 12 in)

HEMP-4X400

4

Yes

Yes

173 cm x 86 cm x 30 cm (68 in x 34 in x 12 in)

HEMP-3X600

3

Yes

Yes

224 cm x 114 cm x 46 cm (88 in x 45 in x 18 in)

HEMP-4X600

4

Yes

Yes

224 cm x 114 cm x 46 cm (88 in x 45 in x 18 in)

HEMP-3X800

3

Yes

Yes

224 cm x 114 cm x 46 cm (88 in x 45 in x 18 in)

HEMP-4X800

4

Yes

Yes

224 cm x 114 cm x 46 cm (88 in x 45 in x 18 in)

HEMP-3X1200

3

Yes

Yes

257 cm x 135 cm x 61 cm (101 in x 53 in x 24 in)

HEMP-4X1200

4

Yes

Yes

257 cm x 135 cm x 61 cm (101 in x 53 in x 24 in)


For other wire numbers or amperages please contact the factory.


 

 

Dual Line Single Phase FiltersETS-Lindgren's LRX "TWIN" (Dual Circuit) Series of Power Line Filters are designed for wall-mounted installation and use on AC or DC power lines.
EMP Commercial and Defense Non-Tempest Powerline Filters SpecsETS-Lindgren's Pulse Protected Powerline Filters with Red Edge™ Technology protects against damage to electronic equipment and loss of data caused by a sudden and intense electromagnetic pulse (EMP) and Intentional Electromagnetic Interference (IEMI).
EMP Commercial and Defense Tempest Powerline Filters​​​​ETS-Lindgren EMP/HEMP Power Line Filters offer excellent multi-stage over-voltage and EMI/RFI protection. <br>
Multiple Circuit Filters LRE Series<p>ETS-Lindgren's LRE Series Multiple Circuit Filters are designed for moderate filtering requirements.<br></p>
Multiple Circuit Panels for LRX FiltersETS-Lindgren's LRX Series Filters are available in NEMA type panels for wall-mounted and floor-standing installations.
One Line Single Phase FiltersETS-Lindgren's LRX Series of Power Line Filters are one line, single phase filters with individual mounting requirements.<br>
Single & Dual Line Filters​​ETS-Lindgren's LRW Series Single & Dual Line Filters are UL Listed and come with mounting penetration and hardware for direct installation through a shielded wall. <br>

Key Features


  •  Protects Against Damage from EMP: 
    • HEMP 
    • IEMI
  • Wide Selection of Current Ratings: 10 Amps to 1200 Amps 
  • Meets or Exceeds MIL-STD-188-125, Hardness Critical Item (HCI), 1 & 2 Point-of-Entry Requirements
  • Acceptance Tested at Little Mountain Test Facility, Hill AFB, Ogden, UT
  • Superior Red Edge Performance Features 
  • For Defense (non-TEMPEST) and Commercial Applications

Literature and Videos


 

 

http://www.ets-lindgren.com/products/filters/6001/600101<a href="/sites/etsauthor/ProductBrochures/General%20Brochures/Test_and_Measurement_Full_Line.pdf"><img alt="" src="/_layouts/15/IMAGES/icpdf.png" />Test_and_Measurement_Full_Line.pdf</a>

 

 

http://www.ets-lindgren.com/products/filters/6001/600101

L o a d i n g

 Catalog-Item Reuse