Product Image

Key Features

  • System Consists of Modular, Hot Galvanized Rigid Steel Structural Panels (No Wooden Parts are Used)
  • Panels Bolted from the Inside or the Outside, Depending on the Purpose and Requirements
  • No Special Tools or Welding Necessary
  • Rooms Easily Dismantled and Reinstalled, Enlarged or Modified
  • Download PDF Datasheet
  • ETS-Lindgren's Series 101 RF shielded construction system meets and substantially exceeds all RF shielding requirements. The modular design is uniquely configured to be dismantled and reinstalled, enlarged or modified due to the panel system (only the gasket and the fasteners have to be replaced). No special tools nor welding are necessary during the installation and no maintenance is necessary after installation.

    Specifications
    View the Series 101 Pan Form Rooms technical specifications below

    Electrical Specifications

    Magnetic: 40 dB @ 1 kHz; 80 dB @ 10 kHz; 120 dB @ 5 MHz to 30 MHz
    Electric : 120 dB @ 1 kHz to 30 MHz
    Planewave: 120 dB @ 30 MHz to 1 GHz
    Microwave: 120 dB @ 1 to 40 GHz

    Charts
    View the Series 101 Pan Form Rooms charts below